2003/629/EC: Commission Decision of 27 August 2003 amending Decision 2000/367/EC establishing a classification system for resistance-to-fire performance for construction products, as regards the inclusion of smoke and heat control products (Text with EEA relevance) (notified under document number C(2003) 2851)

  OJ L 218, 30.8.2003, p. 51–54 (ES, DA, DE, EL, EN, FR, IT, NL, PT, FI, SV)
  CS.ES Chapter 13 Volume 31 P. 427
  ET.ES Chapter 13 Volume 31 P. 427
  HU.ES Chapter 13 Volume 31 P. 427
  LT.ES Chapter 13 Volume 31 P. 427
  LV.ES Chapter 13 Volume 31 P. 427
  MT.ES Chapter 13 Volume 31 P. 427
  PL.ES Chapter 13 Volume 31 P. 427
  SK.ES Chapter 13 Volume 31 P. 427
  SL.ES Chapter 13 Volume 31 P. 427

 DA  DE  EL  EN  ES  FI  FR  IT  NL  PT  SV

Text

ES CS DA DE ET EL EN FR IT LV LT HU MT NL PL PT SK SL FI SV
html html html html html html html html html html html   html html html html html html html html
pdf   pdf pdf   pdf pdf pdf pdf         pdf   pdf     pdf pdf

Dates

Classifications

Miscellaneous information

Relationship between documents

Consolidated versions

Text

Bilingual display : CS DA DE EL EN ES ET FI FR HU IT LT LV MT NL PL PT SK SL SV

Commission Decision

of 27 August 2003

amending Decision 2000/367/EC establishing a classification system for resistance-to-fire performance for construction products, as regards the inclusion of smoke and heat control products

(notified under document number C(2003) 2851)

(Text with EEA relevance)

(2003/629/EC)

THE COMMISSION OF THE EUROPEAN COMMUNITIES,

Having regard to the Treaty establishing the European Community,

Having regard to Council Directive 89/106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of the Member States relating to construction products(1), as amended by Directive 93/68/EEC(2), and in particular Article 20(2) thereof,

Whereas:

(1) Commission Decision 2000/367/EC of 3 May 2000 implementing Council Directive 89/106/EEC as regards the classification of the resistance-to-fire performance of construction products, construction works and parts thereof(3) should, for the purposes of its adaptation to technical progress, also cover smoke and heat control products.

(2) Decision 2000/367/EC should therefore be amended accordingly.

(3) The measures provided for in this Decision are in accordance with the opinion of the Standing Committee on Construction,

HAS ADOPTED THIS DECISION:

Article 1

The Annex to Decision 2000/367/EC is amended in accordance with the Annex to this Decision.

Article 2

This Decision is addressed to the Member States.

Done at Brussels, 27 August 2003.

For the Commission

Erkki Liikanen

Member of the Commission

(1) OJ L 40, 11.2.1989, p. 12.

(2) OJ L 220, 30.8.1993, p. 1.

(3) OJ L 133, 6.6.2000, p. 26.

ANNEX

The Annex to Decision 2000/367/EC is amended as follows.

1. The section entitled "SYMBOLS" is amended as follows:

(a) in the table, the following rows are added:

">TABLE>"

(b) in note 2, "EN 13501-4" is inserted after "EN 13501-3".

2. The section entitled "Classifications" is amended as follows:

(a) point 2 is amended as follows:

(i) in the table applying to walls, classes RE360, REI360, REI-M360 and REW360 are added;

(ii) in the classification part of the table applying to floors and roofs:

- above row "RE", a new row "R" is inserted with class R30,

- classes RE360 and REI360 are added;

(b) in point 3 the words "fire protective coatings, claddings and screens" are replaced by the words "fire protective coatings, boards, renderings, claddings and screens";

(c) point 4 is amended as follows:

(i) in the table applying to "partitions (including those incorporating uninsulated portions)", classes EI-M180 and EI-M240 are added;

(ii) in the table applying to "closures for conveyors and trackbound transportation systems", the text relating to "Notes" is replaced by the following: "The I classification is completed by the addition of the suffix '1' or '2' to indicate which definition of insulation is used. An I classification shall be generated for those cases where the test specimen is a pipe or duct configuration with no assessment of the closure for the conveyor system. The addition of the symbol 'C' indicates that the product also satisfies the 'self-closing' criterion (pass/fail test) (*).";

(iii) the table applying to "wall and ceiling coverings" is replaced by the following:

">TABLE>

Notes

The suffixes '1' and '2' indicate which substrates, fire behaviour criteria and extension rules are used in this classification."

(d) the following point 7 is added:

"7. Products to be used in smoke and heat control systems

The standards cited in this section are under preparation and may be due to revision or upgrade.

>TABLE>

Notes

The classification is completed by the suffix 'single' to indicate suitability for single compartment use only.

In addition, the symbols, 've' and/or 'ho' indicate the suitability for vertical and/or horizontal use.

'S' indicates a leakage rate of less than 5 m3/hr/m2 (All ducts without an 'S' classification must have a leakage rate of less than 10 m3/hr/m2)

'500', '1000', '1500' indicate the suitability for use up to these values of pressure, measured at ambient.

>TABLE>

Notes

The classification is completed by the suffix 'multi' to indicate suitability for multi-compartment use.

In addition, the symbols 've' and/or 'ho' indicate the suitability for vertical and/or horizontal use.

'S' indicates a leakage rate of less than 5 m3/hr/m2 (All ducts without an 'S' classification must have a leakage rate of less than 10 m3/hr/m2)

'500', '1000', '1500' indicate the suitability for use up to these values of pressure, measured at ambient.

>TABLE>

Notes

The classification is completed by the suffix 'single' to indicate suitability for single compartment use.

'HOT 400/30' (high operational temperature) indicates that the damper has the ability to be opened or closed during a period of 30 minutes under temperature conditions below 400 °C (to be used only with E600 classification).

'ved', 'vew' 'vedw' and/or 'hod', 'how' 'hodw' indicate the suitability for vertical and/or horizontal use, together with mounting in a duct or in a wall or both respectively.

'S' indicates a leakage rate of less than 200 m3/hr/m2. All dampers without an 'S' classification must have a leakage rate of less than 360 m3/hr/m2. All damper less than 200 m3/hr/m2 take this value, all dampers between 200 m3/hr/m2 and 360 m3/hr/m2 take the 360 m3/hr/m2 value. Leakage rates are both at ambient and elevated temperatures.

'500', '1000', '1500' indicates the suitability for use up to at these values of under pressure, measured at ambient.

'AA' or 'MA' indicates automatic activation or manual intervention

'io', 'i o', 'i [harr ]o', indicates the performance criteria are satisfied from inside to outside, outside to inside or both respectively.

'C300', 'C10000', 'Cmod' indicates the suitability of the damper for use in smoke control only systems combined smoke control and environmental systems, or modulating dampers used in combined smoke control and environmental systems respectively.

>TABLE>

Notes

The classification is completed by the suffix 'multi' to indicate suitability for multi-compartment use.

'HOT 400/30' (high operational temperature) indicates that the damper has the ability to be opened or closed during a period of 30 minutes under temperature conditions below 400 °C.

'ved', 'vew' 'vedw' and/or 'hod', 'how' 'hodw' indicate the suitability for vertical and/or horizontal use, together with mounting in a duct or in a wall or both respectively.

'S' indicates a leakage rate of less than 200 m3/hr/m2. All dampers without an 'S' classification must have a leakage rate of less than 360 m3/hr/m2. All damper less than 200 m3/hr/m2 take this value, all dampers between 200 m3/hr/m2 and 360 m3/hr/m2 take the 360 m3/hr/m2 value. Leakage rates are both at ambient and elevated temperatures.

'500', '1000', '1500' indicates the suitability for use up to these values of pressure, measured at ambient.

'AA' or 'MA' indicates automatic activation or manual intervention

'io', 'i o', 'i [harr ]o', indicates that the performance criteria are satisfied from inside to outside, outside to inside or both, respectively.

'C300', 'C10000', 'Cmod' indicates the suitability of the damper for use in smoke control only systems, combined smoke control and environmental systems, or modulating dampers used in combined smoke control and environmental systems, respectively.

>TABLE>

Notes

'A' can be any time over 120 minutes.

>TABLE>

Notes

>TABLE>

Notes

Where θ indicates the exposure condition (temperature)."